Nortec ASD Manuel d'utilisateur Page 8

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 12
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 7
-6-
C2
D
GO TO
Always align distributor holes so that steam is discharged
upwards to ensure condensate will remain in the distributor.
H
1/3W
2/3W
W
1/3W1/3W
1/3W
1/3W
Min. W = 8” (203 mm)
Figure #5
Vertical Airflow
WARNING:
·
These installation guidelines apply for duct velocities under 2000 ft/min (610 m/min), please consult factory
for higher velocities.
·
Please make sure no obstacles (elbow, filter, or diffuser) are located after the distributor in the direction of the
airflow closer than the absorption distance calculated for your application.
·
Unless you know the exact absorption distance required for the steam absorption into the air stream, the
distributor should be located at least 8-10 ft (2-3 m) away from any obstacle it may condense on (elbow,
diffuser, filter, etc.).
Vue de la page 7
1 2 3 4 5 6 7 8 9 10 11 12

Commentaires sur ces manuels

Pas de commentaire